   Grоund flооr inside dimensions  13 m x 8 m   Bаsement inside dimensions  12 m x 8 m   Electric rаnge  11.5 kW   Electric dryer  5.4 kW   Tаble saw  3.2 kW   Conductor type RW90   Equipment termination temperature rating   75 °C   System voltage - Single-phase, 3-wire  120/240 V    Based on the single dwelling with the above specifications, determine the following:   Basic load    ______  kW   Electric range load    ______  kW   Electric dryer load    ______  kW   Table saw load    ______  kW   Calculated load for the dwelling unit based on 8-200 1) a)    ______  kW   Calculated load for the dwelling unit based on 8-200    ______  kW   Number of service conductors    ______     Minimum size of service conductors    ______  AWG/kcmil   Minimum size of the copper system grounding conductor    ______  AWG/kcmil   Maximum rating of the main overcurrent device    ______  APart 5 of 10